ACPI: fan: Expose fan performance state information When _FPS indicates variable speed fan support, the thermal cooling device for fan shows max performance state count as "max_state" (greater than or equal to 1). But the thermal cooling device doesn't expose the properties of each performance state. This is not enough for smart fan control user space software, which also considers speed, power and noise level. This change exposes the properties of the fan performance states in the sysfs directory of the ACPI device representing the fan, that is /sys/bus/acpi/devices/devices/INT3404:00 or /sys/bus/platform/devices/PNP0C0B:00. For example: $ ls /sys/bus/acpi/devices/INT3404\:00 description path state0 state11 state4 state7 status hid physical_node state1 state2 state5 state8 subsystem modalias power state10 state3 state6 state9 uevent uid wakeup where each state* attribute lists the properties of a fan performance state in the following format: control_percent:trip_point:speed_rpm:noise_level_mdb:power_mw $ cat /sys/bus/acpi/devices/INT3404\:00/state10 95:0:11600:47500:4500 as documented in Documentation/admin-guide/acpi/fan_performance_states.rst While at it, return the correct error code from acpi_fan_probe() when acpi_fan_get_fps() or acpi_fan_get_fif() fails. Suggested-by: Rafael J. Wysocki <rafael.j.wysocki@intel.com> Signed-off-by: Srinivas Pandruvada <srinivas.pandruvada@linux.intel.com> [ rjw: Subject, changelog, documentation ] Signed-off-by: Rafael J. Wysocki <rafael.j.wysocki@intel.com>
2019-12-13 23:48:40 +00:00
.. SPDX-License-Identifier: GPL-2.0
===========================
ACPI Fan Performance States
===========================
When the optional _FPS object is present under an ACPI device representing a
fan (for example, PNP0C0B or INT3404), the ACPI fan driver creates additional
"state*" attributes in the sysfs directory of the ACPI device in question.
These attributes list properties of fan performance states.
For more information on _FPS refer to the ACPI specification at:
http://uefi.org/specifications
For instance, the contents of the INT3404 ACPI device sysfs directory
may look as follows::
$ ls -l /sys/bus/acpi/devices/INT3404:00/
total 0
...
ACPI: fan: Expose fan performance state information When _FPS indicates variable speed fan support, the thermal cooling device for fan shows max performance state count as "max_state" (greater than or equal to 1). But the thermal cooling device doesn't expose the properties of each performance state. This is not enough for smart fan control user space software, which also considers speed, power and noise level. This change exposes the properties of the fan performance states in the sysfs directory of the ACPI device representing the fan, that is /sys/bus/acpi/devices/devices/INT3404:00 or /sys/bus/platform/devices/PNP0C0B:00. For example: $ ls /sys/bus/acpi/devices/INT3404\:00 description path state0 state11 state4 state7 status hid physical_node state1 state2 state5 state8 subsystem modalias power state10 state3 state6 state9 uevent uid wakeup where each state* attribute lists the properties of a fan performance state in the following format: control_percent:trip_point:speed_rpm:noise_level_mdb:power_mw $ cat /sys/bus/acpi/devices/INT3404\:00/state10 95:0:11600:47500:4500 as documented in Documentation/admin-guide/acpi/fan_performance_states.rst While at it, return the correct error code from acpi_fan_probe() when acpi_fan_get_fps() or acpi_fan_get_fif() fails. Suggested-by: Rafael J. Wysocki <rafael.j.wysocki@intel.com> Signed-off-by: Srinivas Pandruvada <srinivas.pandruvada@linux.intel.com> [ rjw: Subject, changelog, documentation ] Signed-off-by: Rafael J. Wysocki <rafael.j.wysocki@intel.com>
2019-12-13 23:48:40 +00:00
-r--r--r-- 1 root root 4096 Dec 13 20:38 state0
-r--r--r-- 1 root root 4096 Dec 13 20:38 state1
-r--r--r-- 1 root root 4096 Dec 13 20:38 state10
-r--r--r-- 1 root root 4096 Dec 13 20:38 state11
-r--r--r-- 1 root root 4096 Dec 13 20:38 state2
-r--r--r-- 1 root root 4096 Dec 13 20:38 state3
-r--r--r-- 1 root root 4096 Dec 13 20:38 state4
-r--r--r-- 1 root root 4096 Dec 13 20:38 state5
-r--r--r-- 1 root root 4096 Dec 13 20:38 state6
-r--r--r-- 1 root root 4096 Dec 13 20:38 state7
-r--r--r-- 1 root root 4096 Dec 13 20:38 state8
-r--r--r-- 1 root root 4096 Dec 13 20:38 state9
-r--r--r-- 1 root root 4096 Dec 13 01:00 status
...
where each of the "state*" files represents one performance state of the fan
and contains a colon-separated list of 5 integer numbers (fields) with the
following interpretation::
control_percent:trip_point_index:speed_rpm:noise_level_mdb:power_mw
ACPI: fan: Expose fan performance state information When _FPS indicates variable speed fan support, the thermal cooling device for fan shows max performance state count as "max_state" (greater than or equal to 1). But the thermal cooling device doesn't expose the properties of each performance state. This is not enough for smart fan control user space software, which also considers speed, power and noise level. This change exposes the properties of the fan performance states in the sysfs directory of the ACPI device representing the fan, that is /sys/bus/acpi/devices/devices/INT3404:00 or /sys/bus/platform/devices/PNP0C0B:00. For example: $ ls /sys/bus/acpi/devices/INT3404\:00 description path state0 state11 state4 state7 status hid physical_node state1 state2 state5 state8 subsystem modalias power state10 state3 state6 state9 uevent uid wakeup where each state* attribute lists the properties of a fan performance state in the following format: control_percent:trip_point:speed_rpm:noise_level_mdb:power_mw $ cat /sys/bus/acpi/devices/INT3404\:00/state10 95:0:11600:47500:4500 as documented in Documentation/admin-guide/acpi/fan_performance_states.rst While at it, return the correct error code from acpi_fan_probe() when acpi_fan_get_fps() or acpi_fan_get_fif() fails. Suggested-by: Rafael J. Wysocki <rafael.j.wysocki@intel.com> Signed-off-by: Srinivas Pandruvada <srinivas.pandruvada@linux.intel.com> [ rjw: Subject, changelog, documentation ] Signed-off-by: Rafael J. Wysocki <rafael.j.wysocki@intel.com>
2019-12-13 23:48:40 +00:00
* ``control_percent``: The percent value to be used to set the fan speed to a
specific level using the _FSL object (0-100).
* ``trip_point_index``: The active cooling trip point number that corresponds
to this performance state (0-9).
* ``speed_rpm``: Speed of the fan in rotations per minute.
* ``noise_level_mdb``: Audible noise emitted by the fan in this state in
millidecibels.
* ``power_mw``: Power draw of the fan in this state in milliwatts.
For example::
$cat /sys/bus/acpi/devices/INT3404:00/state1
25:0:3200:12500:1250
When a given field is not populated or its value provided by the platform
firmware is invalid, the "not-defined" string is shown instead of the value.
ACPI Fan Fine Grain Control
=============================
When _FIF object specifies support for fine grain control, then fan speed
can be set from 0 to 100% with the recommended minimum "step size" via
_FSL object. User can adjust fan speed using thermal sysfs cooling device.
Here use can look at fan performance states for a reference speed (speed_rpm)
and set it by changing cooling device cur_state. If the fine grain control
is supported then user can also adjust to some other speeds which are
not defined in the performance states.
The support of fine grain control is presented via sysfs attribute
"fine_grain_control". If fine grain control is present, this attribute
will show "1" otherwise "0".
This sysfs attribute is presented in the same directory as performance states.
ACPI Fan Performance Feedback
=============================
The optional _FST object provides status information for the fan device.
This includes field to provide current fan speed in revolutions per minute
at which the fan is rotating.
This speed is presented in the sysfs using the attribute "fan_speed_rpm",
in the same directory as performance states.